banner

Blue e roof-mounted cooling unit

SK 3383500 TopTherm Blue e Roof-Mounted Cooling Unit Total cooling output 1706.07 - 13648.57 BTU/h SK 3383500 TopTherm Blue e Roof-Mounted Cooling Unit Total cooling output 1706.07 - 13648.57 BTU/h SK 3383500 TopTherm Blue e Roof-Mounted Cooling Unit Total cooling output 1706.07 - 13648.57 BTU/h

SK 3383500 TopTherm Blue e Roof-Mounted Cooling Unit Total cooling output 1706.07 - 13648.57 BTU/h

Energy-efficient Blue e roof-mounted cooling units in output categories 1706.07 - 13648.57 BTU/h with e-Comfort controller integrated as standard and electrical condensate evaporation.

Product description

SK cooling unit Blue e, roof-mounted, 3412 BTU/h, 230 V, 1~, 50/60 Hz, carbon steel, WHD: 597 x 417 x 475 mm



Product Introduction

Article no.:

SK 3383500

Version

roof-mounted

Product description

Energy-efficient Blue e roof-mounted cooling units with integral e-Comfort controller and electric condensate evaporation as standard.

Benefits

May be linked to the IoT interface via the Blue e IoT adapter for cooling units with an output of 500 W or higher and e-comfort controllers

Material

Carbon steel

Color

RAL 7035

Supply includes

Condenser with hydrophobic RiNano coating

Integral electric condensate evaporation

Wired ready for connection (plug-in terminal strip)

Drilling template

Fasteners

Total cooling output to DIN EN 14511

Cooling output L35 L35/50 Hz: 1 kW

Cooling output L35 L35/60 Hz: 1.09 kW

Cooling output L35 L50/50 Hz: 0.8 kW

Cooling output L35 L50/60 Hz: 0.81 kW

( Cooling output L35 L35/50 Hz: 3,412 BTU/h

Cooling output L35 L35/60 Hz: 3,719 BTU/h

Cooling output L35 L50/50 Hz: 2,730 BTU/h

Cooling output L35 L50/60 Hz: 2,764 BTU/h )

Rated operating voltage

230 V, 1~, 50 Hz/60 Hz

Note

Due to its low noise level, the roof-mounted cooling unit 3273.500 is also suitable for use in office applications.

Rated current max.

At 50 Hz: 3.1 A

At 60 Hz: 4.5 A

Start-up current (max.)

At 50 Hz: 8.8 A

At 60 Hz: 10.1 A

Air throughput (unimpeded air flow)

External circuit: 1,600 m³/h

Internal circuit: 491 m³/h

( External circuit: 941.7 cfm

Internal circuit: 289 cfm )

Energy efficiency ratio (EER) 50/60 Hz L35 L35

Refrigeration factor L35 L35 (EER) 50 Hz: 2.4

Refrigeration factor L35 L35 (EER) 60 Hz: 1.95

Version

roof-mounted

Dimensions

Width: 597 mm

Height: 417 mm

Depth: 475 mm

( Width: 23.5 ˝

Height: 16.4 ˝

Depth: 18.7 ˝ )

Protection category IP to EN 60 529

External circuit, IP 34

Internal circuit, IP 54

Refrigerant/cooling medium

Refrigerant: R-513A

Quantity: 0.65 kg

Global Warming Potential (GWP): 631

CO₂ equivalent (CO₂e): 0.41 t

( Refrigerant: R-513A

Quantity: 1.4 lb. )

Type of connection (electrical)

Plug-in terminal strip

Duty cycle

100 %

Temperature control

e-Comfort Controller (factory setting +35 °C)

Operating temperature range

10 °C...55 °C

( 50 °F...131 °F )

Operating temperature max @60 Hz

53 °C

( 127 °F )

Storage temperature range

-40 °C...70 °C

( -40 °F...158 °F )

Setting range

20 °C...53 °C

( 68 °F...127 °F )

Rated power Pel

Rated power L35 L35/50 Hz: 0.42 kW

Rated power L35 L35/60 Hz: 0.56 kW

Rated power L35 L50/50 Hz: 0.48 kW

Rated power L35 L50/60 Hz: 0.65 kW

Permissible operating pressure (p. max.)

28 bar

( 406.1 PSI )

Pre-fuse

Miniature circuit-breaker/fuse: 10 A

Packaging unit

1 pc(s).

Net weight

41.8 kg

Gross weight

44 kg

Customs tariff number

84158200

EAN

4028177323216

ETIM 9

EC000855

ETIM 8

EC000855

ECLASS 8.0

27180704

Product description

SK cooling unit Blue e, roof-mounted, 3412 BTU/h, 230 V, 1~, 50/60 Hz, carbon steel, WHD: 597 x 417 x 475 mm


Send Message

Send us a message if you have any questions or request a quote.We will be back to you ASAP!